For extending the Hotwater and Heating Control via Homeassistant, i've made some investigation regarding the following parameters and their settings and valid ranges:
Model: AIT SWCV62k3
Firmware: 3.85.8
1034: ID_Einst_P155_PumpDHWCtrl
Luxtronik Menu Entry = Effizienzpumpe > Steuerung WW.
Sets the pump control mode during hot water generation
1 = Automatic (Pump is regulated to achieve a fixed temperature spread between supply and return)
0 = Manual (Pump is set to fixed speed parameter 1035)
1035: ID_Einst_P155_PumpDHW_RPM
Luxtronik Menu Entry = Effizienzpumpe > Steuerung WW.
Sets the fixed speed of HUP during hot water generation
value 1 - 100 equals setting 1 - 100% in Luxtronik
1041: ID_Einst_P155_PumpDHW_Max
Luxtronik Menu Entry = Effizienzpumpe > Max. Lstg. WW
value 1 - 100 equals setting 1 - 100% in Luxtronik
The valid range that can be set in the Luxtronik is 50 - 100%. Via this interface, lower values can also be written.
I use this to reduce disturbance in the Hot Water Boiler without throttling the flow with valves.
1043: ID_Einst_P155_Sperrband_1
Defines the invalid operating frequency range of the inverter
Luxtronik Menu Entries: Inverter > Sperrband Start / Inverter > Sperrband Stop
Both settings in Luxtronik modify the same value. The values are mapped as a sum of both parameters:
Sperrband Stop: value 65536 - 7864320 equals setting 1 - 120 Hz
Sperrband Start: value 1 - 120 equals setting 1 - 120 Hz
Both value are added for the final parameter value.
Example:
Sperrband Stop 30 Hz = 1966080
Sperrband Start 23 Hz = 23
ID_Einst_P155_Sperrband_1 = 1966080 + 23 = 1966103
1045: ID_Einst_P155_DHW_Freq
Luxtronik Menu Entry = Inverter > Freq. WW
Allows a fixed speed for Hot Water Generation (can be used to mimic the "Target Temperature" Hot water generation mode of the Nibe Heatpump Controllers in combination with parameter 1035)
This parameter is usually only writable with service level access on the luxtronik, but can be written via the interface without issue.
value 0 is Automatic
value 1 - 101 equals setting 20 - 120 Hz
1052: ID_Einst_Warmwasser_extra
Luxtronik Menu Entry = Inverter > Warmwasser
value 0 = Normal
value 1 = Luxus (increased compressor frequency during hot water generation)